ZTX Series Transfer Switch



overview

The GE Zenith Controls ZTX Series of transfer switches is built for residential and light commercial critical/non-life safety applications requiring the dependability and ease of operation found in a power contactor switch. The ZTX transfer switches are designed for standby applications, and incorporate a double-throw, mechanically interlocked contactor mechanism.

features & benefits

The ZTX transfer switches are equipped with the MX60 Control Panel.This microprocessor includes:
- Undervoltage sensing (90% pickup/80% dropout) of the utility source
- Voltage and frequency sensing of the generator source (90% voltage/95% frequency pickup)
- Time Delay Engine Start - 5 seconds (P)
- Time Delay Engine Warmup - Transfer to Generator - 20 seconds (W)
- Time Delay Utility Stabilization/Retransfer to Utility - 5 minutes (T)
- Time Delay Engine Cool Down - 5 minutes (U)
- Indicating LEDs for power availability, switch position and load energized
- Pushbuttons for test, engine start (manual), generator exerciser, timer bypass and program cancel
- Special status annunciation of in-phase transfer and timer operation
- Selectable 7, 14, 21 or 28 day (factory set 28 days) generator exerciser timer
- Diagnostic LED indications in logical one-line configuration
- All time delays are fixed.

The unit is available in open type, NEMA 1 or NEMA 3R enclosures. Additional options include:
- A3/A4 Auxiliary contacts (1 each) closed in utility and generator positions
- Integrated battery charger 1.5A/12V
- Special timer settings

Product Scope
- Ratings 40 to 400 amps (2, 3 or 4 pole)
- UL 1008, CSA and IEC listed to 240 VAC 50/60 Hz
- Double throw, mechanically interlocked contactor mechanism
- Electrically operated, mechanically held
- Designed for standby applications
- Seismic certified to IEEE-693-2005 at HIGH level with 2.5 amplification factor
- Seismic certified to IBC-2006 at Ip=1.5 for z/h less than or equal to 1